10KV SG(B)10 SERIES OF NON ENCAPSULATED DRY TRANSFORMER

The transformer use class C heat-resistant NOMEX paper as insulation,so that the products can reach the requirements of fireproof and waterproof and meet the requirements of environmental protection.During the whole service life,the dry type transformer is extremely good electric performance and mechanical performance.
Submit

Product Parameters

1. Product description  

The transformer use class C heat-resistant NOMEX paper as  insulation,so that the products can reach the requirements of fireproof and waterproof and meet the requirements of environmental protection.During the whole service life,the dry type transformer is extremely good electric performance and mechanical performance.Aging and shrinkage resistance and compression resistance,combined with more powerful elastic,which can make sure that the transformer even use several years later,the coil remain tight structure,and be able to withstand short circuit pressure.Transformer's capacity is 200~3150KVA,insulation class is H grade.


2. Product features

The transformer has these advantages:safe environmental    protection,high insulation level,no melting under the 250℃,no toxic gases released under the750℃,no burning fuel and combustion-supporting under 800℃ flame light for about 40  minutes,no harm to human body,and also no pollution to the environment.We could recover the transformer after life period ,and it is an ideal product in environmental protection.


3. Scope of application

The transformer is suitable for high fire safety requirements,big load fluctuation and filthy wet environments.Such as:the airport,subway,power plant,metallurgy,hospitals,high-rise building,shopping center,tall,densely populated area,and the important place for petrochemical, nuclear power,nuclear  submarines.It is the ideal equipment for power distribution.


4. Technical parameters

(Model)

(Capacity)

(KVA)

Voltage (kv)

Connection

symbol

No-Load

Losses

(W)

Load

Losses

No-Lad  u%ent

UK

120℃ (%)

Sound

Level(dB)

 Weight (Kg)

Outline Dimension

(W×L×H,mm)

Installation dimensions

(mm)

(HV)

(LV)

SG10-100/10

100

6

±5%

6.3

±2

x2.5%

10

0.4

Dyn11

Yyn0

400

1690

1.8





4

65

610

650x980x1010

550x550

SG10-125/10

125

470

1980

1.6

66

720

650×1050x1015

550x550

SG10-160/10

160

540

2280

1.6

830

650×1060x1055

550x550

SGB10-200/10

200

620

2710

1.4

67

955

650x1100×1090

550x550

SGB10-250/10

250

720

2960

1.4

1100

760×1130×1115

660x660

SGB10-315/10

315

880

3730

1.2

69

1450

760×1270×1240

660x660

SGB10-400/10

400

980

4280

1.2

1580

760x1315×1300

660x660

SGB10-500/10

500

1160

5230

1.2

70

1750

760x1410×1330

660x660

SGB10-630/10

630

1300

6400

1.0

6

71

1970

760×1490×1350

820x660

SGB10-800/10

800

1520

7460

1.0

72

2125

920x1520×1410

820×820

SGB10-1000/10

1000

1770

8760

1.0

2400

920×1590×1460

820x820

SGB10-1250/10

1250

2090

10370

1.0

74

3090

920×1720x1575

820x820

SGB10-1600/10

1600

2450

12580

1.0

75

3930

920×1780x1610

1070x820

SGB10-2000/10

2000

3050

15560

0.8

77

4260

1170×1900x1670

1070×1070

SGB10-2500/10

2500

3600

18450

0.8

78

4580

1170x1950x1810

1070x1070

Related products